楊(yang)雲(雲)
安(an)科(ke)瑞(rui)電(dian)氣股份有(you)限(xian)公(gong)司 上海嘉(jia)定(ding) 201801
【摘要】:在(zai)高層建(jian)築中采(cai)用的剩余(yu)電(dian)流式電(dian)氣火災監控(kong)系統,其特(te)點在(zai)於(yu)漏(lou)電(dian)監控(kong)方面(mian)屬(shu)於(yu)早期預報警系統,與(yu)火(huo)災自動報警系統不同(tong)的是(shi),電(dian)氣火災監控(kong)系統可(ke)以在(zai)火(huo)災發(fa)生前(qian)報警,從而避免損(sun)失(shi),而火(huo)災自動報警系統只(zhi)能在確(que)認火災發(fa)生後(hou)減少損(sun)失(shi)。
【關(guan)鍵詞(ci)】:建(jian)築電(dian)氣;剩余(yu)電(dian)流式電(dian)氣火災監控(kong)系統
0引(yin)言
剩余(yu)電(dian)流式電(dian)氣火災監控(kong)系統由(you)電(dian)氣火災監控(kong)裝(zhuang)置(zhi)、剩余(yu)電(dian)流式電(dian)氣火災監控(kong)探(tan)測器以及(ji)測(ce)溫式(shi)電(dian)氣火災監控(kong)探(tan)測器等(deng)3個(ge)基本(ben)的設(she)備組成(cheng)。其中火(huo)災監控(kong)探(tan)測器又由監控(kong)探(tan)測器和剩余(yu)電(dian)流互(hu)感器(分(fen)對(dui)插式、閉(bi)合(he)式兩(liang)種(zhong))組成(cheng),而測(ce)溫(wen)式電(dian)氣火災監控(kong)探(tan)測器由(you)監控(kong)探(tan)測器和測溫(wen)傳感器組(zu)成(cheng)。
1原理與應用
1.1設計(ji)依據
近(jin)年(nian)來我國(guo)為(wei)加(jia)強(qiang)電(dian)氣火災防範(fan)的監控(kong)力度,相(xiang)繼制訂或(huo)修改了(le)相(xiang)關(guan)國家(jia)標準(zhun)規(gui)範(fan),為剩余(yu)電(dian)流式電(dian)氣火災監控(kong)系統的設(she)計(ji)及應用提(ti)供了(le)依據(ju),主(zhu)要(yao)包(bao)括(kuo):①GB50045—95(2005版)《高層民用建(jian)築設計(ji)防火規(gui)範(fan)》第9.5.1條:高層建(jian)築內火災危險性大、人(ren)員(yuan)密集等(deng)場(chang)所(suo)宜(yi)設置漏(lou)電(dian)火災報警系統;②GB50016—2006(建(jian)築設計(ji)防火規(gui)範(fan)》第11.2.7條:各(ge)種(zhong)類型(xing)的影(ying)劇(ju)院、館所(suo)、倉(cang)庫(ku)、住宅(zhai)小區(qu)、醫院(yuan)、商(shang)店(dian)、學校等(deng)場(chang)所(suo)宜(yi)設置剩余(yu)電(dian)流動作(zuo)電(dian)氣火災監控(kong)系統;③《建(jian)築電(dian)氣火災預防(fang)要(yao)求(qiu)和檢測方法(fa)》有(you)關(guan)條文(wen)也(ye)明(ming)確(que)要(yao)求(qiu)“應(ying)在電(dian)源進(jin)線端(duan)設(she)置自動切斷(duan)電(dian)源或(huo)報警的剩余(yu)電(dian)流動作(zuo)保(bao)護器”;④GB14287—2OO5(電(dian)氣火災監控(kong)系統》規(gui)定(ding)了(le)相(xiang)應(ying)產品(pin)要(yao)滿足(zu)的技(ji)術要求(qiu);⑤JGJ16—2008《民用建(jian)築電(dian)氣設計(ji)規範(fan)》第13.12篇規定了(le)防火(huo)剩余(yu)電(dian)流動作(zuo)報警系統設(she)計(ji)應滿足(zu)的要(yao)求(qiu)。
1.2監控(kong)原理
漏(lou)電(dian)監控(kong)報警主(zhu)要(yao)是(shi)利用裝(zhuang)在(zai)被(bei)監控(kong)配(pei)電(dian)線路(lu)上(shang)的剩余(yu)電(dian)流互(hu)感器檢測線路(lu)上(shang)的漏(lou)電(dian)流來實(shi)現。剩余(yu)電(dian)流互(hu)感器本(ben)質(zhi)上是(shi)壹個(ge)高靈(ling)敏(min)的電(dian)流互(hu)感器,它(ta)能(neng)檢測出配(pei)電(dian)線路(lu)上(shang)小到(dao)幾(ji)毫安或(huo)十(shi)幾毫(hao)安的微(wei)小漏(lou)電(dian)流,而漏(lou)電(dian)流檢測則是(shi)依據剩余(yu)電(dian)流原理來確(que)定(ding)的。當(dang)配(pei)電(dian)線路(lu)中3條相(xiang)線和1條零(ling)線共(gong)同(tong)穿(chuan)過剩余(yu)電(dian)流互(hu)感器的鐵(tie)芯(xin)線圈(quan)時(shi),在正(zheng)常(chang)情況下(xia)它(ta)們(men)的電(dian)流矢量(liang)和為零(ling),則互(hu)感器的線圈(quan)不會感應出任何電(dian)流;但當(dang)任何壹(yi)條相(xiang)線或(huo)者零(ling)線有(you)壹(yi)部分(fen)電(dian)流在互(hu)感器之後(hou)分(fen)流到(dao)大地(即漏(lou)電(dian)),此時在(zai)互(hu)感器處它(ta)們(men)的電(dian)流矢量(liang)和就不為零(ling)了(le),而互(hu)感器的線圈(quan)也(ye)就(jiu)感應(ying)出相(xiang)應(ying)的漏(lou)電(dian)電(dian)流,故(gu)稱(cheng)為剩余(yu)電(dian)流。把檢測到(dao)的剩余(yu)電(dian)流處理後與監控(kong)裝(zhuang)置(zhi)設(she)定值(zhi)進(jin)行比(bi)較(jiao),壹(yi)旦達(da)到(dao)和超過設(she)定值(zhi),與剩余(yu)電(dian)流互(hu)感器連接(jie)的電(dian)氣火災監控(kong)探(tan)測器即發(fa)出漏(lou)電(dian)報警,並(bing)同(tong)時(shi)輸(shu)出脫扣跳閘信號(hao)切斷(duan)相(xiang)應(ying)故(gu)障(zhang)線路(lu)電(dian)源。漏(lou)電(dian)檢測如(ru)圖1。
1.3實(shi)施(shi)方案
通過在(zai)被監控(kong)電(dian)力配(pei)電(dian)線路(lu)主(zhu)開(kai)關下(xia)方安裝(zhuang)剩余(yu)電(dian)流式電(dian)氣火災探(tan)測器和剩余(yu)電(dian)流互(hu)感器,並(bing)通(tong)過信(xin)號總(zong)線實(shi)現與(yu)電(dian)氣火災監控(kong)主(zhu)機間(jian)的信(xin)息通訊(xun)來(lai)實(shi)現對(dui)電(dian)氣火災的監控(kong)。根據工(gong)程設計(ji)的實(shi)際需(xu)要,監控(kong)系統可(ke)在(zai)整個(ge)電(dian)力系統的任何壹(yi)條配(pei)電(dian)線路(lu)上(shang)安裝(zhuang),並(bing)承(cheng)擔對(dui)安裝(zhuang)節(jie)點(dian)以下(xia)的相(xiang)關(guan)電(dian)氣線路(lu)和設備的漏(lou)電(dian)監控(kong)報警,起(qi)到(dao)脫(tuo)扣跳閘保(bao)護的作(zuo)用。同(tong)時(shi)也(ye)能(neng)根據電(dian)力設計(ji)的需(xu)要(yao)而組(zu)成(cheng)二級或(huo)多(duo)級監控(kong)實(shi)施(shi)保(bao)護,並(bing)實(shi)現在(zai)相(xiang)應(ying)線路(lu)漏(lou)電(dian)故(gu)障(zhang)報警時有(you)選(xuan)擇(ze)性地脫(tuo)扣跳閘保(bao)護。
3安科瑞電(dian)氣火災監控(kong)雲系統架構和硬(ying)件(jian)選(xuan)型(xing)
安(an)科(ke)瑞電(dian)氣推出的電(dian)氣火災監控(kong)雲系統采(cai)用自主(zhu)研發(fa)的剩余(yu)電(dian)流互(hu)感器、溫(wen)度(du)傳感器和電(dian)氣火災探(tan)測器、故(gu)障(zhang)電(dian)弧探(tan)測器和電(dian)氣防火(huo)限(xian)流式保(bao)護器,對(dui)引發(fa)電(dian)氣火災的主(zhu)要(yao)因(yin)素(su)(導線溫(wen)度(du)、電(dian)流、剩余(yu)電(dian)流、故(gu)障(zhang)電(dian)弧等(deng))進(jin)行不間(jian)斷(duan)的數(shu)據與(yu)統計(ji)分(fen)析(xi),並(bing)將(jiang)發(fa)現的各(ge)種(zhong)隱患信(xin)息及時(shi)推(tui)送(song)給學校管(guan)理人(ren)員(yuan),指導學校實(shi)現時(shi)間(jian)的排查和治(zhi)理,達(da)到(dao)潛(qian)在(zai)電(dian)氣火災隱患,實(shi)現“防(fang)患(huan)於(yu)未(wei)然”的目(mu)的。
用戶可(ke)以利用PC、手(shou)機、平(ping)板(ban)電(dian)腦等(deng)多(duo)種(zhong)終端實(shi)現對(dui)平臺(tai)的訪(fang)問(wen),查詢包(bao)括(kuo)系統信(xin)息、實(shi)時(shi)數(shu)據、報記(ji)錄等(deng)在(zai)內(nei)的各(ge)種(zhong)信息,使(shi)用方便。利用該系統為(wei)用戶提(ti)供的低成(cheng)本服務,能(neng)有(you)提(ti)升企業(ye)的消防(fang)管(guan)理和電(dian)氣設備水平(ping),防範(fan)重大惡(e)性(xing)火災財產(chan)損失(shi)、尤(you)其是(shi)重大惡(e)性(xing)人(ren)員(yuan)傷(shang)亡責(ze)任的發(fa)生。
本(ben)系統的整體(ti)結構如(ru)圖所(suo)示(shi):
3.1硬(ying)件(jian)配(pei)置(zhi):
平(ping)臺(tai)服(fu)務器:建(jian)議按照(zhao)我方提(ti)供配(pei)置(zhi)標準(zhun)購(gou)買,或(huo)者客(ke)戶自己租用阿裏(li)雲資(zi)源(yuan)。
推(tui)薦(jian)硬(ying)件(jian)配(pei)置(zhi):(如(ru)申請(qing)阿裏(li)雲可忽略)
現場(chang)硬(ying)件(jian)配(pei)置(zhi)
方案壹:100A以下(xia)回路,開(kai)口式(shi)互(hu)感器
方案二:100A以下(xia)回路,普(pu)通互(hu)感器,會(hui)增加(jia)施(shi)工(gong)量
方案三:100A以下(xia)回路,普(pu)通電(dian)流互(hu)感器,探(tan)測器和無線模(mo)塊(kuai)分(fen)開(kai),可適(shi)用多(duo)回路
配(pei)置(zhi)針(zhen)對(dui)1個(ge)回路,剩余(yu)電(dian)流互(hu)感器根據現場(chang)回路電(dian)流大小選(xuan)擇(ze)。
3.2運行(xing)條件(jian):
1)瀏(liu)覽(lan)器運(yun)行(xing)設備:
臺(tai)式(shi)電(dian)腦,手(shou)機、平(ping)板(ban)等(deng)移(yi)動(dong)端(duan)設(she)備。
2)瀏覽(lan)器端(duan)運(yun)行環境:
Windows系統下(xia)使(shi)用火狐、360(速(su)模式(shi))等(deng)瀏(liu)覽(lan)器訪(fang)問(wen)。
3.3主(zhu)要(yao)技(ji)術指標:
數(shu)據上(shang)傳頻率:2分(fen)鐘(zhong)
通(tong)信(xin)方式:RS485、2G/3G/4G
並(bing)發(fa)訪(fang)問(wen)量(liang):>=10000
歷史(shi)數(shu)據存儲:>=3年(nian)
4結(jie)語
電(dian)氣火災監控(kong)系統是(shi)近幾年(nian)出現的新技(ji)術,對(dui)於(yu)它(ta)的設(she)計(ji)和應用還處在(zai)摸(mo)索實(shi)踐(jian)階段(duan),包(bao)括(kuo)產品(pin)標準(zhun)和設計(ji)規範(fan)都(dou)在逐步完善(shan)中。做(zuo)為(wei)設計(ji)人(ren)員(yuan),我們(men)應(ying)當(dang)在工(gong)程設計(ji)的實(shi)際應(ying)用中不斷(duan)積累(lei)經驗(yan),總結(jie)教(jiao)訓(xun),使(shi)電(dian)氣火災監控(kong)系統在(zai)防(fang)範(fan)電(dian)氣火災方面(mian)充(chong)分(fen)的發(fa)揮(hui)出它的作(zuo)用。
參(can)考文(wen)獻(xian):
[1]GB50016—2006建(jian)築設計(ji)防火規(gui)範(fan)[S].
[2]GB50045-95(2005版).高層民用建(jian)築設計(ji)防火規(gui)範(fan)[S].
[3]廖建(jian)海.建(jian)築電(dian)氣剩余(yu)電(dian)流式電(dian)氣火災監控(kong)系統的應(ying)用.建(jian)築理論(lun)與(yu)設計(ji)[J].
[4]安科瑞(rui)企業(ye)微(wei)電(dian)網設計(ji)與應用手(shou)冊(ce),2020.06版.